Model No.: KE8302


Electricity 3 Phase Energy Meter Calibration With Isolated Current Transformer


Electricity 3 Phase Energy Meter Calibration With Isolated Current Transformer

 

  1. Usage: Auto Electric meter test and calibration
  2. Accuracy Class:  0.05%
  3. Meter position: 6 / 12 / 24 position
  4. Phase: Three Phase
  5. Name: energy meter test equipment, Electric meter test bench
  6. Power: Electronic
  7. Voltage Output: 3×(24V – 300V)
  8. Current Output:  3×(1mA – 120A)
  9. Operating Temperature: -10°C -- +40°C
  10. Adopt ICT to test I-P close link meters

 

3 Phase Energy Meter Test Bench With Isolated Current Transformer (ICT)

 

KE8302 is used for the test of three phase four wire (3P4W) and three phase three wire (3P3W) electrical and mechanical meters, multi-function meters, smart meters, and multi-user meters of electric power company, meter manufacturing company and institutes of metrology, it can also do the test and calibration of single phase energy meters

 

Highlight:

  • Integrated/separated aluminum alloy structure, light and reliable, flexible choices
  • Meter positions can be chosen from 6-24
  • Adopt ICT to test I-P close link meters
  • Auto protections of short circuit of voltage, open circuit of current, and overload
  • Test of neutral current (optional)
  • Auto mark locking increases the efficiency of test
  • Full automatic, semi automatic and manual operation available
  • Supporting bar code input, which increase the efficiency of input
  • Simultaneous test of the meters with same specification, different constants and different classes.
  • Adopt multi-serial port system, realizing the parallel communication of computer and the tested meters( optional)
  • Test of tilt impact (optional)
  • Forward and reverse active energy/ Forward and reverse reactive energy error test
  • Creeping and starting test
  • Standard deviation, 24 hour variation test
  • Timing error test
  • Influencing quantity test of voltage, frequency, harmonic
  • Calibration and verification of constant
  • Register indicating value, register combination error test
  • Powerful computer management system, easy and user-friendly
  • Perfect database management makes the storage, searching, and viewing of the data possible, and the data can be converted and exported in other forms

 

Main specifications:

 

 

KE8302-6

KE8302-12

KE8302-24

Number of meter position

6

12

24

Accuracy

± 0.05%

Voltage output

Output range (P-N)

3×(24V – 300V)

Output power of voltage

3×100VA

3×250VA

3×500VA

Resolution

Better than ± 0.01%

Stability

Better than ± 0.02% / 150s

Load regulation rate

Better than ± 0.01%

Distortion factor

Better than  ± 0.3% (linear resistance load)

Harmonics output

bigPhoto
 Mr. Vivi Zhang

Tel: 86-20-62220181
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Related Products

Company Info

Guangzhou Kingrise Enterprises Co., Ltd. [China (Mainland)]


Business Type:Manufacturer
City: Guangzhou
Province/State: Guangdong
Country/Region: China (Mainland)

You May Like:

Product (165)